Food safety

Optimising your CIP processes

Met de oplossingen van ifm electronic kan u CIP/SIP-reinigingen perfect onder controle houden en optimaliseren om kosten (energie, water, reinigingsproduct) te besparen.
Met de oplossingen van ifm electronic kan u CIP/SIP-reinigingen perfect onder controle houden en optimaliseren om kosten (energie, water, reinigingsproduct) te besparen.

Food safety is the cornerstone of food production. CIP and SIP (Cleaning and Sterilising In Place) play an important role in ensuring hygiene in pipes and closed systems. CIP/SIP is a process involving a precise interplay of mechanical forces, time, temperature and chemicals. With solutions from ifm electronic, you can keep CIP/SIP cleaning processes fully under control and optimise them to save costs on energy, water and cleaning products.

CIP and SIP are largely identical processes, consisting of several steps to ensure that pipes and closed process systems are perfectly clean again. This is achieved by alternating cleaning with alkaline and acidic solutions with rinsing using hot water. SIP also includes a thermal or chemical disinfection step. Philippe Briers, Project Leader Smart Factory at ifm: “Four factors determine the efficiency of CIP/SIP processes: mechanical forces, temperature, chemicals and time. The longer the first three factors act, the better the cleaning process. However, companies need to keep this time as short as possible so they can resume production quickly. Finding the right compromise is therefore crucial.” ifm electronic has the sensor technology needed to monitor this interplay precisely. And by bringing all the signals together in moneo, users get clear, plug-and-play dashboards that point them straight towards further optimisation opportunities or can be used to record cleaning processes accurately.

With its LDL sensors, ifm electronic has added conductivity sensors to its range, designed specifically for applications of this kind.

Optimising flow rates

The first factor we will look at is mechanical forces. The water or chemicals need to flow at a sufficiently high rate to remove any contaminants from the pipes. “Flow sensors are the conventional way to address this. They measure flow velocity, which should ideally be between 1.5 m/s and 2.1 m/s. If the flow rate is too low, there is too little turbulence, resulting in inadequate cleaning. A higher flow rate does not improve cleaning results and simply leads to unnecessary energy consumption,” says Briers. With a broad range of magnetic-inductive flow meters, ifm can meet users’ needs. Key advantages include the digital IO-Link signal, which can convert the flow rate in l/min into a value in m/s. Users with analogue signals can use the DP2200 module for reliable conversion to IO-Link.

Always the right temperature

Each cleaning step requires a specific temperature. Briers: “Temperature is therefore a key factor in cleaning quality. It is important to know the temperature throughout the tank. Measuring at both the inlet and outlet gives us the absolute and relative values, ensuring that users know the required temperatures have been reached for the specified periods.” A standout product in this field is the TCC231 sensor, which combines two measurement principles (PTC and NTC) and two independent probes in a single sensor housing. “You always get a clear and reliable value in parallel. If drift starts to occur, you know immediately and can intervene before a shutdown becomes necessary.”

The TCC231 sensor combines two measurement principles (PTC and NTC) and two independent probes in a single sensor housing. “You always get a clear and reliable value in parallel.”

Accurate chemical dosing

Finally, chemicals also play a role. Here too, accurate dosing is important to avoid unnecessary costs. “Conductivity measurements are used to measure the concentration of cleaning products and determine the quality of the rinse water.” With its LDL sensors, ifm electronic has added conductivity sensors to its range, designed specifically for applications of this kind. “They can also provide temperature readings. As with temperature sensors, it is worth checking both the inlet and outlet of the tank. This confirms that the chemicals have been able to do their job and tells us when no particles remain in the rinse water,” explains Briers. The new LDL 101 can also detect very low concentrations, for example in applications involving demineralised water.

Measurement data are recorded continuously for historical data analysis. This makes it possible to identify opportunities for optimisation and savings.

Ease of use with moneo

But what can you learn from the values captured by these sensors? That is where moneo comes in. Briers: “Measurement data are recorded continuously for historical data analysis. This makes it possible to identify opportunities for optimisation and savings. Sensor data thus becomes relevant process information. Integrated alarm management also enables users to respond quickly to changing process parameters. Ease of use is really the priority here.” The ‘calculated values’ offered by moneo are also worth highlighting. Users can quickly convert values into the required unit themselves. “In a PLC, this involves a fair amount of programming. With moneo, it is simply a matter of drag and drop.”    

Question about this story? Ask your question

Keep following this

Get an email when a new story is published. No account needed.

What you follow
  • ThemeFood safety from design to audit
  • SubjectFood safety
Share this article

Follow on FoodTec

Follow

Follow a project or company and you’ll receive an email whenever a new story appears. Follow a theme or topic and you’ll receive a weekly roundup. No account or password needed: every email includes a link to what you follow.